Model FC901 contains one (1), built-in DACT and two (2) NACs.
Standard Operating Unit 50-point Cerberus PRO FACPĥ0-point Cerberus PRO FACP Model FC901 is an addressable FACP that provides a costeffective solution for simple fire-alarm-system applications. The Photoelectric Smoke Detector uses microcontroller circuitry and surface-mount technology for peak dependability. For example, the Multi-Criteria Fire / CO Detector is cutting-edge technology for specialized applications such as carbon-monoxide detection compared to standardized detectors.
In conjunction with these new, improved FACPs is a state-of-the-art line of intelligent detectors. The 252 and 504-point systems are networkable. SureWireTMaddressable-loop technology is supported by Cerberus PRO.Ĭerberus PRO is ideally suited for small and mid-market applications by providing 50, 252 and 504-point addressable fire-alarm-control-panel (FACP). Through the use of its unique multiprocessor ’Network’ design – along with its ability to utilize intelligent detection devices – Cerberus PRO epitomizes a flexible and highly configurable fire system. Each Cerberus PRO system provides easy operation via its push-button soft keys a backlit LCD screen, and a (4) four-way navigation push button all located in the upper portion of each panel. Product Overview Cerberus PRO, a comprehensive fire-protection system from Siemens Fire Safety, is a technologically advanced fire-and-life-safety system.
NEC 760 power-limited circuits UL 864-compliant Optional notification-appliance-circuit (NAC) expansion module Up to 3.0 amps (24VDC) load per output Module used for 252/ 504-point systems
Supports single-person, ‘Walk Test’ Sprinkler Supervision End-user ‘Help’ screens Multiple command stations Supports pre-action, deluge and Sinorix®-agent releasing for 252 / 504point systems Releasing-valve monitoringĭetector Sensitivity Readout / Printout per NFPA 72Īlarm verification (by device or zone) Degrade-mode operation Logic-controlled output functions Optional city-tie / leased-line module Distributed processing Gas Alarm events for CO detection, per NFPA 720 for the 252 / 504-point systems Intelligent / analog detection circuits: ‘Class A’ or ‘Class B’ FirePrint TM SureWireTM addressable-loop technology Patented polarity-insensitive detection circuits LED-option provides LED annunciation of system activity Backlit liquid-crystal display (LCD) Light-emitting diodes (LEDs) for: Power, Alarm, Supervisory, Silenced, Ground Fault, Trouble, and systemstatus LEDs Alarm command has a larger, distinctive LED
Universal AC power input: 120VAC or 240VAC 50 / 60Hz 2.0A max.įully field programmable, via a Windows® -laptop PC Built-in strobe synchronization protocol Global annunciation and control capability Several relay commands: Alarm, Trouble, Supervisory, etc. RS 485 interface Four-way navigation menu with extended-views capabilityĪutomatic environmental compensation for smoke detectorsģ00-Watts is rated at 11.5 Amps 170-Watts is rated at 6.5 Amps
Off-line reports can be viewed the customconfiguration programming tool EEPROM software compatible Powerful, but user-friendly system interfaceĥ,000-event history-logging capability with on-line and off-line reports Supervised remote printer, via the Remote Peripheral Module Remote viewing for the 252point and 504-point systems Standard 50-point, 252-point and 504-point fire systemsĬerberus® DMS Danger Management Station can monitor, control up to 16 Model FC922, FC924 FACPs Cerberus PRO A comprehensive fire-protection system ARCHITECT AND ENGINEER SPECIFICATIONS